![]() |
If this is your first visit, be sure to check out the FAQ by clicking the link above. You may have to register before you can post: click the register link above to proceed. To start viewing messages, select the forum that you want to visit from the selection below. |
|
|
Thread Tools | Display Modes |
|
#1
|
|||
|
|||
![]()
On Jun 19, 12:58 am, "Montblack" Y4_NOT!...
wrote: ("GeorgeB" wrote) There is a guy (a lawyer, darnit) who has done some research in this; I understand that he was involved in a complaint against the wild numbers used in advertising ... take alook at http://users.goldengate.net/~kbrady/motors.pdffor some interesting info My old memory has it that motors are rated by the heat that they can dissipate, rather than the torque/ revs that they produce, or electrical energy they consume. An example would be: if we have a constant load that will raise the frame temperature to an acceptable level, then that torque/rpm is the rated hp. The motor will produce much more torque, but it will overheat at that hp output. You see the effect of this rating on the frame style, with open frame having a much higher hp rating than a sealed explosion proof motor, with similar dimensions and windings. The really wild ratings are the "protection ratings", where they advertise the hp load required to trip the overheat circuit breaker, by definition that is more hp than the motor can safely produce. How is that for useless information ? |
#2
|
|||
|
|||
![]()
On Jun 18, 7:25 pm, GeorgeB wrote:
Based on the units with bigger motors, the HP is a marketing game, not real. Industry assumes ... ASSUMES ... about 4 cfm (to 100 psi) per horsepower. Small units will be less efficient ...maybe 3 cfm. Large (50 hp+) units will be a little better, perhaps 4.4 or so. It is often missed that capacity is INLET air. This issue has been beaten to death on the rec.crafts.metalworking discussion group. Everyone knows that Sears compressors are wildly overrated. I was in the transportation air brake industry for years, and me and my guys rebuilt about 12,000 compressors in that time and tested every one of them on a dyno. We found that, as you have said, that one HP will pump around 4 CFM. We had the cutout at 120 psi, but of course, as also mentioned, there's nowhere near 4 CFM being delivered at 120 psi. The 4 CFM is free air, at atmospheric pressure. A really good compressor has as little volume as absolutely possible when the piston is at TDC. This is to drive out as much of the compressed air as possible; any air left in the cylinder at TDC will expand as the piston travels downward again and so the intake valves won't open until the cylinder pressure drops below atmospheric pressure. A cheap compressor might have so much unswept volume that, at the higher pressures, the intakes don't open until the piston is halfway down. Not efficient at all. Unswept volume includes that between the piston and head, whatever cavities the intake and discharge valves may have, and so forth. So the CFM rating is a zero discharge pressure, and it will drop, depending on the efficiency and overall design of the compressor, to considerably less as the tank pressure rises. You can't take cylinder area and multiply it by stroke and RPM to get a reliable CFM figure, but I think that's what the retailers do. You will be disappointed if you have a 4 CFM spray gun and expect the 4 CFM compressor to keep up with it. The spray gun requires 4 CFM at around 40 or 60 psi, the compressor is rated at zero. Dan |
#3
|
|||
|
|||
![]() |
#4
|
|||
|
|||
![]() "RST Engineering" wrote But then you multiplied that times two for "starting" wattage for a couple of seconds to give 1725 watts under start and then times three for starting under some volume of air left in the compressor reservoir or about 2600 watts. Most air compressors have a valve that lets off the air pressure in the line between the pump and the tank, when they shut off. You can tell if it has this feature, by seeing a little air line going to the pressure on/off switch. You may not need to multiply so big for starting with air in the tank. -- Jim in NC |
#5
|
|||
|
|||
![]()
On Mon, 18 Jun 2007 13:49:59 -0700, "RST Engineering"
wrote: I thought I had this compressor power thing down to a pretty good science until they started screwing around with "rated watts" and "peak power" and all that crap that makes their compressor look really good until you go to use it. Back when we were using "real" horsepower I used a figure of 750 (to make it easy to calculate, I believe 746 is the actual number) watts per horsepower and an efficiency factor of 85% so that a one horse motor would take 860 watts to do the actual work. But then you multiplied that times two for "starting" wattage for a couple of seconds to give 1725 watts under start and then times three for starting under some volume of air left in the compressor reservoir or about 2600 watts. That presses my 2200 watt continuous duty (2800 watts peak) fairly close to the load limit, but certainly gives a margin for error that seems reasonable. Before I tell elebendy bazillion Kitplanes readers that the Harbor Freight Subaru 2200 watt generator will drive the Sears 1 horse compressor (and even worse, buy the Sears compressor only to not have it work), will somebody please do a reality check on me for horsepower/watts for this lashup. (Note ... convert watts to amperes by dividing watts by 120 volts). 860w=7a 1725w=14a 2600w=21a Sears and Harbor Freight are damned near clueless about this sort of stuff. If anybody has a source I can reference for running/starting/starting under load for air compressors it would be well received. I'd LIKE to buy a 3/4 horse compressor but they go from the kiddie's 1/4 horse toy straight to one horse with darned little in between. Jim Jim, Living off-grid, and generating most of my own power from renewables, I am somewhat familiar with your issue. Although your approach may make theoretical sense, in the real world (as you found out) it frequently doesn't work. The startup surge for an electric motor is given by a parameter called "locked rotor amps" (means pretty much what it says). This can either be measured (with a clamp-on ammeter), or derived from a letter on the nameplate of the actual motor multiplied by the running amps. A compressor is one of the more difficult devices to start. Without specific data, I would figure starting amps to be at least five times the nameplate amperage rating. Fugedabout trying to convert nameplate HP to startup surge. It might be less, or not. So far as your generator is concerned, it is likely that the ratings assume a power factor of 1. But an induction motor, such as is in your compressor, will have a power factor considerably less than 1. This further increases the amount of "real power" the generator must supply. And may also explain why the nameplate amperage rating seems higher than what you predict by using HP and an assumed efficiency. I happen to have a Sears 1HP compressor (1.5HP Peak). Mine has a nameplate rating of 10.5A @ 120V. I could not see/locate the nameplate on the motor itself, so I figured a 52.5A startup surge (5X). My inverter has a 78A peak capacity (46A continuous) so I figured things would work -- and they have. Your 2800W peak generator translates to 23.3A at 120VAC. If you have the same Sears compressor as I do, I'm not surprised that the generator will have a problem starting it. Another issue that comes up with compressors has to do with flat spots on the rotor as they age. This causes them to draw the locked rotor amp startup current for a longer period of time when new. This can also cause an otherwise adequately sized system to "blow" on startup, occasionally. --ron |
#6
|
|||
|
|||
![]()
On Jun 24, 5:20 am, Ron Rosenfeld wrote:
... Ron, what peak starting current should I expect on a single-phase, 240V, 3/4h.p., running current=7.8A motor used to lift my hangar door? I want to rig up a genny to lift the door during a power failure. The gear train on the door is rigged so that all of the cables are slack (i.e. only motor inertial) when the motor starts. |
#7
|
|||
|
|||
![]() |
#8
|
|||
|
|||
![]() "Ron Rosenfeld" wrote A problem with small, inexpensive, gasoline fueled generators is that, unless you are religious about exercising them, they usually won't start when you need them. An exception to that rule is a Honda generator. I'm not a foreign car guy, or anything like that; quite the opposite. My dad had one that would sit for a couple of years, and it would start on the first or second pull, with fresh gas in the tank. It is amazing how many other uses come up, once you have a generator sitting around. -- Jim in NC |
#9
|
|||
|
|||
![]()
On Wed, 27 Jun 2007 01:05:26 -0400, "Morgans"
wrote: "Ron Rosenfeld" wrote A problem with small, inexpensive, gasoline fueled generators is that, unless you are religious about exercising them, they usually won't start when you need them. An exception to that rule is a Honda generator. I'm not a foreign car guy, or anything like that; quite the opposite. My dad had one that would sit for a couple of years, and it would start on the first or second pull, with fresh gas in the tank. It is amazing how many other uses come up, once you have a generator sitting around. Mine is 9500 watts continuous. It doesn't even have the option of a pull starter. I don't think I could pull it even if it did. I keep the tank full. When I shut it down I turn the gas off and let it dry out the carb. It's on wheels, but it'd take a truck to haul it so it could be called portable. OTOH it'd take three and preferably four men to put it in the truck. If it were in the shop I could do that with an engine hoist. I fire it up about every other month and let it run for about 10 minutes. In the winter I have to keep a small heat lamp on the battery. It'll run about 10 to 12 hours powering the whole house sans air conditioner (except for the little spare one stuck in the bedroom window) on 10 gallons. I had a little 4000 watt Coleman that used twice as much gas, but it was kinda portable and made a whole lot more noise. I purchased it new, *after* Y2K when there were lots of them available at half price and less. In the last 6 1/2 years I have well over 100 hours on it powering the house. Lots of power outages due to poor line maintenance and we are about 2 miles from the city limits and just over a mile from the substation. As for other uses, with help I some times pull it out of the generator shed and use it to power my 180 amp MIG welder. It's been a while but IIRC the engine doesn't even change pitch when welding. |
#10
|
|||
|
|||
![]()
On Wed, 27 Jun 2007 01:05:26 -0400, "Morgans"
wrote: "Ron Rosenfeld" wrote A problem with small, inexpensive, gasoline fueled generators is that, unless you are religious about exercising them, they usually won't start when you need them. An exception to that rule is a Honda generator. I'm not a foreign car guy, or anything like that; quite the opposite. My dad had one that would sit for a couple of years, and it would start on the first or second pull, with fresh gas in the tank. It is amazing how many other uses come up, once you have a generator sitting around. One problem is that frequently, after sitting around for a few years, there isn't fresh gas in the tank! (I should have been more specific as to the reasons). --ron |
Thread Tools | |
Display Modes | |
|
|
![]() |
||||
Thread | Thread Starter | Forum | Replies | Last Post |
Air Compressor Horsepower/Wattage/Amperage | RST Engineering | Owning | 32 | June 30th 07 12:47 AM |
more horsepower | T-Bone | Piloting | 11 | March 20th 06 10:56 PM |
Lycoming Horsepower Calculation? | Mark Doble | Home Built | 1 | June 20th 05 10:46 PM |
Thermals and Horsepower | Ken Kochanski (KK) | Soaring | 14 | January 9th 05 05:50 PM |
Horsepower | Andre | Home Built | 3 | July 18th 03 10:50 AM |